Pipe Size vs. Pressure Drop: Worked Example

Compare 1½, 2 and 2½ inch Schedule 40 pipes at 10 m³/h. See velocity, friction loss and head, then reproduce each case in the calculator.

Tools / Worked examples

The question and answer

At 10 m³/h, how much does pressure drop change when a 50 m water line increases from NPS 1½ to NPS 2 or NPS 2½?

Total loss falls from 71.226 kPa to 21.048 kPa with NPS 2, then to 8.957 kPa with NPS 2½. These are hydraulic comparisons at a fixed flow, not a claim that the largest pipe is the most economical choice.

1. Hold the duty constant

InputValue
Flow10 m³/h
Straight length50 m
Density / dynamic viscosity998.2 kg/m³ / 1.002 mPa·s
Roughness0.045 mm
Total fitting K4.0, referenced to each candidate pipe bore
Elevation / equipment losses0 m / 0 kPa
BoundariesPipe inlet and pipe outlet of equal bore; α = 1
Required outlet pressure0 kPa gauge for this loss-only comparison

Use the actual inside diameter, not the nominal size. Schedule 40 IDs below are 1.610, 2.067 and 2.469 inches converted with 25.4 mm/in. See the pipe schedule reference. A fixed total K of 4 is a simplifying assumption; real fitting arrangements and K values may change with size.

2. Compare the calculated results

SizeID (mm)v (m/s)Darcy fPipe loss (kPa)Fittings (kPa)Total (kPa)Head (m)
NPS 1½: download system40.89402.11490.022824062.2978.92971.2267.276
NPS 2: download system52.50181.28310.022697017.7613.28721.0482.150
NPS 2½: download system62.71260.89930.02281737.3431.6158.9570.915

Open each downloaded JSON with the multi-section calculator's Open system file control. Each is a single-section case. The single-pipe calculator uses the same shared friction method.

ΔP = (fD L/D + ΣK) × ρv²/2

For NPS 2: v = 1.283096 m/s, Re = 67,109 and fD = 0.02269697. Straight-pipe loss is 17.761 kPa and fitting loss is 3.287 kPa, giving 21.048 kPa.

3. Apply a velocity target, then check pressure

Suppose this project uses an illustrative maximum velocity of 1.5 m/s. In the pipe sizing calculator enter 10 m³/h, 1.5 m/s and Schedule 40. The minimum ID is 48.558 mm, and the first listed size meeting it is NPS 2. Its actual velocity is 1.2831 m/s.

The 1.5 m/s target is a scenario assumption, not a universal limit. Pressure budget, noise, erosion, solids transport, installation cost and operating hours can change the choice. NPS 2 reduces this case's loss by about 70.4% relative to NPS 1½. NPS 2½ reduces it by about 87.4%, but its installed cost is not evaluated here.

At fixed flow, straight-pipe loss scales approximately with fD/D⁵. The friction factor also changes with Reynolds number and relative roughness, so recalculate each candidate instead of treating that fifth-power relation as exact.

What this comparison leaves out

There is no static elevation, exchanger, control-valve requirement or pump curve in this example. Add those terms for a complete system. Keep velocity head separate from irreversible losses, use the correct bore for every fitting, and check mechanical design independently.

Method background: US EPA EPANET documentation. Related tools: single-pipe pressure drop and roughness reference.

Keep exploring