Multi-Section Pipe Pump Head: Worked Example

Calculate pump head through two pipe sizes, fittings, a heat exchanger and a 5 m rise. Follow the pressure breakdown and download the example.

Tools / Worked examples

The question and answer

Transfer 10 m³/h of water between two large, open tanks. The receiving liquid surface is 5 m higher. The line includes two inside diameters, a reducer, fittings and a heat exchanger.

Calculated duty: 12.654 m of water head, equivalent to 123.871 kPa at this flow. This is the system requirement before any design allowance. Select a pump using its curve at 10 m³/h and check suction conditions separately.

Download the JSON file, open the calculator, then use its Open system file control. No account is needed.

1. Define the boundaries and inputs

InputValue
Flow10 m³/h = 0.00277778 m³/s
Density; dynamic viscosity998.2 kg/m³; 1.002 mPa·s (cP), rounded water values near 20°C
Pipe roughness0.045 mm in both sections, an assumed condition
Inlet / outlet boundaryReservoir surface / reservoir surface
Required outlet gauge pressure0 kPa; both tanks are open to the same atmosphere
Kinetic energy coefficients1 at both boundaries and in both sections
SectionLength / inside diameterElevation changeLoss assumptions
Supply line30 m / 52.5 mm0 mEntrance K = 0.5; four elbows K = 0.9 each, all referenced to 52.5 mm
Equipment line20 m / 40.9 mm+5 mReducer K = 0.2 at section entrance, based on 40.9 mm; restriction K = 2 at 35 mm bore; exit K = 1 at 40.9 mm; exchanger ΔP = 25 kPa

The K values and exchanger pressure drop are explicit teaching assumptions at this flow, not universal fitting data. Use custom K entries to reproduce them. Enter the reducer once under the second section's transition, not again as a fitting. The 35 mm restriction bore is deliberately different from its pipe bore.

2. Calculate velocity and friction

v = 4Q/(πD²)
Re = ρvD/μ
ΔPpipe = fD × (L/D) × ρv²/2
ΔPfitting = K × ρvfitting²/2
SectionVelocity (m/s)Reynolds numberDarcy f
Supply line1.28318671120.0226970
Equipment line2.11427861460.0228238

Both sections are turbulent. The calculator solves Colebrook for the Darcy friction factor. At the 35 mm restriction, velocity is 2.88716 m/s and the K = 2 pressure loss is 8.32071 kPa. Using the 40.9 mm pipe velocity there would understate the loss.

3. Add losses and elevation

ContributionPressure requirement (kPa)
Supply pipe10.658
Supply entrance + elbows3.369
Equipment pipe24.900
35 mm restriction + reservoir exit10.552
Reducer0.446
Heat exchanger25.000
Total irreversible losses74.926
5 m elevation, ρgΔz48.945
Net boundary velocity change0.000
Total system requirement123.871
H = ΔPsystem/(ρg) = 123,871.091 / (998.2 × 9.80665) = 12.6541 m

The section table shows local velocity-change terms as water enters and changes pipe size. The outlet boundary removes the remaining kinetic term. They sum to zero between reservoir surfaces. The explicit exit K = 1 represents irreversible dissipation and still belongs in the loss total.

For these open-tank boundaries, interpret the calculator's system ΔP and equivalent head as the pump energy addition needed. Its “required inlet gauge pressure” is an equivalent pressure requirement, not the actual atmospheric pressure above the open supply tank.

4. Use the result correctly

Keep the 5 m static rise separate from friction: larger pipe can reduce losses but cannot eliminate the elevation requirement. The exchanger loss may change with flow; do not reuse 25 kPa blindly at another duty. Check pump efficiency, operating range, NPSH, piping pressure rating and the full system curve before selecting equipment.

Next: compare pipe sizes, then check NPSH available.

Method reference: US EPA EPANET documentation covers pipe-network hydraulics and head-loss methods. The numerical example here uses Frictionless Calc's multi-section engine, not EPANET.

Keep exploring