Choose what to solve for
Enter flow rate and inside diameter to calculate total friction pressure drop.
Pipe
Fluid & Flow
Fittings
Liquid-water properties reference ↗ · Pure water, 0–99°C at 100 kPa absolute.
Calculate
Friction loss, pressure drop, and head loss
For a full circular pipe, the Darcy–Weisbach equation gives straight-pipe head loss as h = f(L/D)v²/(2g). Fittings add ΣK v²/(2g) on the applicable velocity basis. Pressure loss is ΔP = ρgh. Head loss is expressed as a height of the flowing liquid; pressure drop is expressed in pressure units such as kPa or psi.
Use this online pipe friction loss calculator for water or another single-phase liquid by entering its density and dynamic viscosity. Select units beside each input, enter actual inside diameter and absolute roughness, then add the fittings in that section. The results separate straight-pipe and fitting losses.
For different pipe sizes in series, elevation changes, or equipment losses, use the Multi-Section Pipe System Calculator. For a size comparison, see the pipe size and pressure drop worked example.
PVC pipe friction loss: use the actual bore
Nominal PVC pipe size is not its inside diameter. Schedule and wall thickness affect the bore, so check the dimensions for the selected product. For example, Charlotte Pipe lists a 2-inch Schedule 40 PVC pipe with a nominal inside diameter of 2.067 inches (52.5018 mm).
Example: enter 30 m of straight pipe, 52.5018 mm inside diameter, 5 m³/h of water at 20°C, density 998.21 kg/m³, dynamic viscosity 1.0016 cP, and an assumed absolute roughness of 0.0015 mm. With no fittings and the calculated Darcy factor, the result is approximately 2.695 kPa pressure loss (0.2753 m of water head). Add the actual fittings to calculate the section's total loss.
The roughness is an illustrative smooth-pipe assumption, not a guarantee for every PVC installation. Check pipe roughness guidance and water properties by temperature when setting up your own calculation. Product dimensions: Charlotte Pipe plastics technical catalog.
HDPE pipe friction loss: check diameter and dimension ratio
HDPE pipes with the same outside diameter can have different bores because their dimension ratios (DR) and wall thicknesses differ. Use the manufacturer's flow diameter or applicable dimensional data, including wall tolerances; do not enter outside diameter as inside diameter.
Diameter comparison: for 30 m of straight pipe carrying 5 m³/h of water at 20°C (density 998.21 kg/m³ and viscosity 1.0016 cP), a 50 mm actual bore gives about 3.389 kPa friction loss, while a 45 mm bore gives about 5.602 kPa. Both calculations use zero roughness as an ideal smooth-wall comparison, no fittings, and the calculated Darcy factor. These are illustrative bores, not dimensions assigned to a particular HDPE size or DR.
For a real installation, enter a supported roughness value and include fittings and valves. See the Plastics Pipe Institute handbook, Chapter 6 for PE piping design and flow-diameter guidance.
Does this calculator use Hazen–Williams?
No. This calculator uses Darcy–Weisbach with a Reynolds-dependent Darcy friction factor, or your supplied Darcy factor. It does not accept a Hazen–Williams C coefficient. C is not absolute roughness and cannot be entered in the roughness field or the Darcy-factor override. When checking a Hazen–Williams water calculation, compare the methods using the same flow, actual bore, length, and fitting assumptions.
How to use the pipe friction loss calculator
Choose ΔP, Q, or D at the top. Flow and diameter are solved by repeatedly evaluating the same Darcy–Weisbach and fitting-loss model. Each solution is back-checked against the entered pressure drop. Diameter is the actual inside diameter; fitting geometry ratios stay fixed as diameter changes. A positive available friction pressure drop is required for Q and D. Negative path-specific fitting K values are supported in ΔP mode only because they can make the inverse problem non-unique.
This calculator estimates frictional pressure loss through one constant-flow, constant-inside-diameter pipe section. Straight-pipe loss is calculated with the Darcy-Weisbach equation, while fittings and valves are added through loss coefficients. Use the actual inside diameter of the pipe, the fluid properties at the expected operating temperature, the design flow rate, and the fittings that are physically in that section.
The total pressure drop shown above is the sum of straight-pipe friction and the selected fitting losses. It is a frictional loss, not the complete pressure requirement for an entire process. If the line changes elevation, discharges into a vessel at a different pressure, passes through equipment with its own pressure drop, or includes a pump or turbine, those effects must be handled separately in the system energy balance.
When to use it
- Single-phase liquid flow through a full circular pipe.
- A pipe section with one flow rate and one inside diameter.
- Preliminary sizing, line-loss checks, pump-system calculations, and comparison of piping alternatives.
- Systems where density and viscosity can reasonably be treated as constant through the section.
For a branched network, calculate each constant-flow section separately. A tee or wye can be included in the section containing the junction, but the downstream branches should use their own branch flow rates and diameters.
Core assumptions
- The fluid is single phase and behaves approximately as a Newtonian fluid.
- The pipe is full, circular, and represented by one actual inside diameter.
- Density, viscosity, and roughness are constant over the modeled section.
- Fitting coefficients represent the selected geometry and operating condition closely enough for engineering estimation.
- Elevation head, vessel pressure differences, heat transfer, pumps, control-system behavior, and equipment pressure drops are outside this calculation unless entered separately as a loss coefficient.
Common mistakes
- Using nominal pipe size instead of actual inside diameter. Pressure drop is very sensitive to diameter because diameter changes both velocity and the L/D term.
- Mixing Darcy and Fanning friction factors. This calculator uses the Darcy friction factor. The Fanning factor is one quarter of the Darcy value.
- Using the wrong viscosity. Enter dynamic viscosity here, not kinematic viscosity. Fluid viscosity can change substantially with temperature.
- Using roughness with the wrong units. Absolute roughness and diameter are converted internally, but the roughness value must correspond to the pipe material and condition you actually intend to model.
- Double-counting fittings. Do not add an equivalent length for a fitting and also add its K value unless you intentionally want both losses.
- Using the wrong velocity basis for a junction K. Tee and wye coefficients are path-specific. This calculator uses the combined-leg reference basis described in the fitting input.
- Treating a partially open valve like a fully open valve. Use vendor data or a custom K when the valve position or trim differs materially from the built-in case.
How to interpret the result
Pressure loss increases rapidly with velocity. In turbulent flow, doubling flow through the same pipe often produces roughly four times the frictional loss, although the exact change also depends on the friction factor. If fittings dominate the result, inspect the fitting breakdown. If straight pipe dominates, diameter, length, flow rate, and roughness are usually the main levers.
A negative path-specific tee or wye K can occur with some junction correlations because K is defined from pressure differences and a selected reference velocity. It does not mean the fitting creates energy.
Related tools and reference
Use the Reynolds Number Calculator to check flow regime, the Darcy Friction Factor Calculator to inspect f directly, and the K Factor ↔ Equivalent Length Calculator when converting loss methods.
Reference background: the U.S. Department of Energy fluid-flow handbook discusses head loss, Darcy friction, Reynolds number, and equivalent-length methods. DOE fluid-flow handbook.
K-factor reference
K-Factor Guide ↗ · Look up typical fitting losses and check velocity bases, fT correlations, equivalent length, and valve data.
Darcy or Fanning?
Darcy vs. Fanning reference ↗ · Compare the definitions, convert friction factors, and check which equation to use.
Equation values and input guide
Select pressure loss, flow or bore as the unknown. Use a single constant-flow section and match all fitting coefficients to their stated velocity basis. Read the fitting breakdown alongside the pipe-friction result.
- Q, V, A
- Volume flow, average velocity and internal flow area: V = Q/A, A = πD²/4. SI equation units are m³/s, m/s and m².
- D, L, ε
- Actual inside diameter, straight-pipe length and absolute wall roughness. Use the same length units in L/D and ε/D.
- ρ, μ, Re
- Operating density, dynamic viscosity and Reynolds number Re = ρVD/μ. SI units are kg/m³ and Pa·s; Reynolds number is dimensionless.
- f
- Darcy friction factor calculated from Re and roughness, or supplied as an override. Fanning f must be multiplied by four before use here.
- K, ΣK
- A dimensionless fitting loss coefficient and the sum of the applicable fitting coefficients. Fitting pressure loss is KρVref²/2 on the specified reference velocity basis.
- fT, n, Le/D
- Fixed-reference fully turbulent friction factor, its fitting multiplier, and equivalent-length ratio. These are alternate fitting-loss representations, not additional straight-pipe length to count twice.
- β, θ, r/d
- Fitting diameter ratio, branch angle and bend-radius/diameter ratio. Follow each fitting’s input label for which diameters and legs define its ratio.
- ΔP, hL, g
- Friction pressure loss in Pa, loss head ΔP/(ρg) in m of flowing fluid, and gravitational acceleration 9.80665 m/s². These exclude elevation and boundary pressure requirements.
Use the unit selectors beside the inputs. Units shown in the equations must be consistent when checking the math by hand.
