Heat Exchanger: Worked Example

Expected answer
599,000 Btu/h · cold outlet 110°F

Size the thermal conductance of a counterflow exchanger from two mass flows and the hot outlet temperature.

Open calculator

1. Calculator Inputs

Select units before entering values.

Calculator fieldValue / setting
ArrangementCounterflow
Temperature / mass flow / duty / UA units°F / lb/h / Btu/h / Btu/(h·°F)
Hot inlet / cold inlet200 / 80 °F
Hot / cold specific heat4.18 / 4.18 kJ/(kg·K)
Known hot / cold mass flow10,000 / 20,000 lb/h
Known hot outlet140 °F
Known boxesSelect only hot mass flow, cold mass flow and hot outlet
Cold outlet, duty and UAUncheck these three boxes; they are calculated
Optional ULeave blank

2. Step-by-step Math

Hot-side energy balance

ṁh = 10000 × 0.45359237 / 3600 = 1.259978806 kg/s
ΔTh = (200−140)/1.8 ≈ 33.3 K
Q = ṁh cp ΔTh ≈ 176 kW
Q = 599025.508742 Btu/h

Use temperature differences without the 32-degree offset. Specific heat is entered in kJ/(kg·K).

Cold outlet and counterflow LMTD

Tc,out = 80 + (10000/20000)(200−140) = 110°F
ΔT1 = 200−110 = 90°F; ΔT2 = 140−80 = 60°F
LMTD = (90−60)/ln(90/60) ≈ 74°F

The terminal differences pair opposite ends of the exchanger.

Required conductance

UA = Q/LMTD = 599025.508742/73.989103871
UA = 8096.131422 Btu/(h·°F)
Effectiveness = (200−140)/(200−80) = 0.5

UA is conductance, not area. Area requires a separately supplied overall heat-transfer coefficient.

3. Compare Your Answers

Keep full precision until the final result. Display rounding may differ; compare answers rounded to three significant figures; retain unrounded intermediate values.

ResultExpected answerYour answer
Duty599,000 Btu/h__________
Cold outlet110°F__________
LMTD74°F__________
UA8,100 Btu/(h·°F)__________
Effectiveness / NTU50% / 0.811__________

Second check

Uncheck hot outlet and check UA instead. Enter 8096.131422 Btu/(h·°F), keeping both mass flows known. The calculated hot and cold outlets return to 140°F and 110°F.

4. Assumptions and Method

Steady counterflow, constant specific heats, no phase change or ambient heat loss. This example uses an ideal counterflow arrangement without a multipass correction. Select exactly three independent known quantities.

Equation definitions and implementation: open calculator. See also calculation methodology.