Heat Exchanger Calculator

1. Set the exchanger and fluid properties

Area = UA/U. Use an overall coefficient based on the same heat-transfer area. This does not add a thermal constraint.

Inlet temperatures and both specific heats are always inputs. cp = 4.18 kJ/(kg·K) is an approximate water example; enter appropriate mean-temperature properties for each fluid. No property database or phase-change model is used.

Hot and cold streams in a heat exchangerHot streamCold streamCounterflow

2. Choose exactly three independent known values

Check Known input for a value you want to specify. Uncheck it to let the calculator solve for it. A dashed field is an output. Start with a preset, then adjust values or switches.

Solve for

Solve for

Solve for

Solve for

Solve for

Solve for

UA is U × area. Leave Known input unchecked to solve UA = duty ÷ LMTD. How is UA calculated?

Liquid-water properties reference ↗ · Pure water, 0–99°C at 100 kPa absolute.

An unchecked value is not used in the equations. More than three known values blocks the solve; compare additional measured values with the outputs separately.

How to use this calculator

The calculator balances heat leaving the hot fluid with heat entering the cold fluid. You can use it to find the required exchanger conductance (UA), or predict outlet temperatures when UA is known.

1. Enter the fluid conditions

Choose counterflow or parallel flow, select your units, and enter both inlet temperatures and specific heats. Specific heat, cp, is the energy needed to warm a unit mass by one degree. Use a representative value for each fluid over its temperature range.

The cp fields always use kJ/(kg·K), including when other inputs use US units. For example, 1 Btu/(lb·°F) = 4.1868 kJ/(kg·K).

2. Choose what you know

Check exactly three independent values in section 2. The calculator solves the other three. These presets are useful starting points:

  • Size: flows + hot outlet. Enter both mass flows and the desired hot outlet temperature. The calculator finds heat duty, cold outlet temperature and required UA.
  • Rate: flows + UA. Enter both mass flows and an existing exchanger’s UA. The calculator finds heat duty and both outlet temperatures.
  • Balance: duty + outlets. Enter heat duty and both outlet temperatures. The calculator finds both mass flows and UA.

3. Calculate and review

Select Calculate heat exchanger. Review the solved values, temperature differences and heat-balance check. If you have additional measurements, compare them with the results.

Why does the calculator reject some combinations?

Duty, hot flow and hot outlet temperature all describe the same hot-side energy balance. Together they do not provide enough information about the cold side or UA. The same problem occurs with duty, cold flow and cold outlet temperature. Choose a preset or replace one of those values with an independent value. More than three checked values are blocked.

How UA is calculated

UA describes how much heat an exchanger can transfer for a given temperature difference. It combines the overall heat transfer coefficient U and the heat transfer surface area A:

UA = U × A = Q / LMTD

Here Q is the heat transfer rate (duty), and LMTD is the effective temperature difference between the fluids. UA can be calculated from flows and temperatures without knowing U or area separately.

Step 1: Find the heat duty

When hot flow and hot outlet temperature are known, multiply mass flow by specific heat and the hot fluid’s temperature drop:

Q = ṁhot × cp,hot × (Th,in − Th,out)

ṁhot is hot mass flow, cp,hot is hot specific heat, and Th,in / Th,out are hot inlet/outlet temperatures. Use kg/s, kJ/(kg·K) and a temperature difference in K to obtain kW. Consistent lb/h, Btu/(lb·°F) and °F give Btu/h.

Step 2: Find the cold outlet temperature

The same heat warms the cold fluid. Divide duty by the cold flow and specific heat, then add the cold inlet temperature:

Tc,out = Tc,in + Q / (ṁcold × cp,cold)

Tc,in / Tc,out are cold inlet/outlet temperatures; ṁcold and cp,cold are cold mass flow and specific heat. Equivalently, the cold-side balance is Q = ṁcold × cp,cold × (Tc,out − Tc,in).

Step 3: Find the effective temperature difference

The temperature gap between the fluids changes along the exchanger. LMTD (logarithmic mean temperature difference) combines the gaps at its two ends.

Temperature differences at the two ends
ArrangementΔT₁ΔT₂
Counterflow: fluids travel in opposite directionsTh,in − Tc,outTh,out − Tc,in
Parallel flow: fluids travel in the same directionTh,in − Tc,inTh,out − Tc,out
LMTD = (ΔT₁ − ΔT₂) / ln(ΔT₁ / ΔT₂)

ln means natural logarithm. When the two differences are equal, LMTD equals either one. Both differences must be positive. In counterflow, the cold outlet can be warmer than the hot outlet because those outlets are at opposite ends.

Step 4: Divide duty by LMTD

UA = Q / LMTD

Duty in kW divided by LMTD in K gives UA in kW/K. Duty in Btu/h divided by LMTD in °F gives UA in Btu/(h·°F). A difference of 1 K equals a difference of 1°C.

If UA is already known, the solver finds duty and outlet temperatures that satisfy both heat balances and Q = UA × LMTD together.

Example: calculate the required UA

Select counterflow and the Size: flows + hot outlet preset. Choose lb/h, °F, Btu/h and Btu/(h·°F), then enter:

Example inputs
InputHot fluidCold fluid
Mass flow10,000 lb/h20,000 lb/h
Inlet temperature200°F80°F
Outlet temperature140°F (known)Leave unchecked
Specific heat input4.1868 kJ/(kg·K)4.1868 kJ/(kg·K)

Leave duty and UA unchecked. For the hand calculation below, the entered specific heat equals 1 Btu/(lb·°F).

  1. Duty: 10,000 × 1 × (200 − 140) = 600,000 Btu/h.
  2. Cold outlet: 80 + 600,000 / (20,000 × 1) = 110°F.
  3. End differences: 200 − 110 = 90°F; 140 − 80 = 60°F. LMTD = (90 − 60) / ln(90/60) = 74.0°F.
  4. Required UA: 600,000 / 74.0 ≈ 8,110 Btu/(h·°F).

See another complete worked example.

How to calculate heat transfer area

To turn UA into surface area, enter an overall heat transfer coefficient U in section 1. The calculator then uses:

A = UA / U

U measures heat transfer per unit area and temperature difference. Obtain it from vendor data, measurements with a known area, or a separate calculation of fluid-film, wall and fouling resistances. Use the same area basis as the surface you want to size.

The optional U field uses W/(m²·K). With UA in kW/K, the area calculation is A = 1000 × UA/U, giving m². US conductance units are converted internally.

U is used only to calculate area. You can leave it blank and still calculate UA. The thermal balances determine the product UA; they cannot determine U and A separately.

What the results mean

Heat duty and temperature approach

Heat duty Q is the heat transferred each second or hour, shown in kW or Btu/h. Minimum terminal approach is the smaller of the two end temperature differences. A very small approach means the fluids nearly reach the same temperature at one end.

Effectiveness

Effectiveness compares actual duty with the maximum possible duty for the entered inlet temperatures and flows:

Effectiveness = Q / [Cmin × (Th,in − Tc,in)]

The heat capacity rates are Ch = ṁhot × cp,hot and Cc = ṁcold × cp,cold. They describe how much heat each stream needs per degree of temperature change. Cmin is the smaller of the two, in power per degree. Effectiveness is dimensionless; a value of 0.70 means 70% of the maximum duty.

Number of transfer units (NTU)

NTU = UA / Cmin

NTU compares exchanger conductance with the smaller stream heat capacity rate. Use matching units for UA and Cmin; their ratio is dimensionless.

Heat transfer area

This result appears when you supply U. It is the surface through which heat passes, rather than the flow area inside a pipe.

Assumptions and limits

  • Steady operation with both fluids remaining in one phase. No boiling, condensation or freezing.
  • Constant representative specific heats and overall conductance, with no heat lost to the surroundings.
  • Ideal counterflow or parallel flow. Crossflow and multipass arrangements with correction factors are not included.
  • Positive flows, duty and end temperature differences. Zero temperature approach cannot be solved as a finite positive-duty case.
  • Fluid properties, pressure drop, detailed geometry and changes in fouling must be evaluated separately. Area is a preliminary sizing result.

References

Known-value selection was inspired by TLK Energy’s calculator. This tool uses its own constant-property model.