Pipe Insulation Heat Loss: Worked Example

Expected answer
3,010 Btu/h over 100 ft

Estimate steady radial heat loss from a 100 ft pipe with 1 inch of insulation. The pipe outside diameter is 2.375 inches. Treat conductivity and the external surface coefficient as constant supplied values.

Open calculator

1. Calculator Inputs

Select the units below before entering the numbers. These are fixed benchmark inputs for checking the calculator.

Calculator fieldValueUnit / setting
Pipe outside diameter2.375in
Radial insulation thickness1in
Insulated pipe length100ft
Pipe outer-wall temperature200°F
Ambient temperature70°F
Insulation conductivity, k0.025Btu/(h·ft·°F)
External surface coefficient, h2Btu/(h·ft²·°F)

2. Step-by-step Math

Calculate the inner and outer insulation radii

r₁ = 2.375 / 24 ≈ 0.099 ft
r₂ = r₁ + 1/12 ≈ 0.182 ft
ΔT = 200 − 70 = 130°F

The insulation is 1 inch thick radially, so it increases the overall diameter by 2 inches to 4.375 inches.

Calculate thermal resistance per unit length

R′insulation = ln(r₂/r₁)/(2πk) = 3.889168009257 h·ft·°F/Btu
R′outside = 1/(2πr₂h) = 0.436539272481 h·ft·°F/Btu
R′total = 4.325707281738 h·ft·°F/Btu

Use the natural logarithm. These are resistance-per-length factors: dividing temperature difference by their sum gives heat rate per foot.

Calculate heat loss and outer-surface temperature

q′ = ΔT / R′total = 130 / 4.325707281738
q′ = 30.052888819 Btu/(h·ft) = 28.896431391 W/m
Q = q′L = 30.052888819 × 100 = 3,005.288881863 Btu/h
Tsurface = Tambient + q′R′outside
Tsurface = 70 + 30.052888819 × 0.436539272481
Tsurface ≈ 83.1°F

The insulation outer surface lies between the ambient and pipe-wall temperatures.

Compare with a bare pipe at the same h

q′bare = 2πr₁hΔT = 161.661121966 Btu/(h·ft)
Reduction = 100 × (1 − q′/q′bare) ≈ 81.4%

The comparison holds h and wall temperature fixed. A real bare pipe may have a different effective surface coefficient.

3. Compare Your Answers

Keep full precision during the calculation. The calculator may display fewer digits; compare answers rounded to three significant figures; retain unrounded intermediate values.

ResultExpected answerYour answer
Heat loss per length30.1 Btu/(h·ft)__________
Total heat loss3,010 Btu/h / 881 W__________
Outer-surface temperature83.1°F__________
Reduction relative to modelled bare pipe81.4%__________

Second check

Set insulation thickness to zero. The cylindrical conduction resistance becomes zero, predicted heat loss becomes 162 Btu/(h·ft), and surface temperature equals the specified 200°F pipe-wall temperature.

4. Assumptions and Method

The model starts at the specified pipe outer-wall temperature, so it excludes internal convection and pipe-wall resistance. It assumes steady one-dimensional radial transfer, constant k and h, and no end or support losses. Radiation is not calculated separately; include it in an appropriate effective external coefficient if needed.

Equation definitions and implementation: Pipe Insulation Heat Loss Calculator. See also calculation methodology and other worked examples.