AI Chips in Space — Heat Transfer Worked Example

Expected answer
7.28 kW from a 100 ft² panel

A hot panel conducts heat through aluminum and a coating, then radiates it to space. The emitting surface settles at about 173.94°F.

The engineering question

How much heat can a warm panel reject in vacuum, and how much panel area would an orbital computing facility need? This example follows the radiator concept explored on Musk Be Kidding. It uses a new, illustrative aluminum-and-coating stack so the conduction and radiation calculations can be checked together. The dimensions and conductivities below are assumed engineering inputs. The hot boundary represents a uniformly heated panel backing.

The larger scenario uses 1 GW of computing load plus 20% facility overhead, giving 1.2 GW of heat. It is a speculative sizing exercise. Read the original AI chips in space thermal analysis.

1. Calculator Inputs

Use the load link above, or enter these values. Select units before entering numbers.

InputValue
Solve forHeat transfer
Side A temperature175°F, fixed panel backing temperature
Area100 ft² of emitting face
Layer 1 — aluminum panel0.125 in, k = 120 Btu/(h·ft·°F)
Layer 2 — radiative coating0.005 in, k = 0.1 Btu/(h·ft·°F)
Last elementConvection film labeled Vacuum boundary
Side B radiationEnabled, emissivity 0.90
Side B vacuum boundaryEnabled — h is ignored and convection is zero
Side B surrounding temperature3 K
Side B bulk temperature3 K — unused by the zero-convection boundary
Side A radiationDisabled
Result temperature unit°F

2. Heat Through the Layers

At steady state, the heat entering the backing must pass through both layers and leave the coating. The common area assumption treats heating as uniform across the panel.

R″aluminum = (0.125/12) / 120 = 0.000086806 h·ft²·°F/Btu
R″coating = (0.005/12) / 0.1 = 0.004166667 h·ft²·°F/Btu
R″layers = 0.004253472 h·ft²·°F/Btu
          = 0.000749080 m²·K/W

The coating contributes most of this particular through-thickness resistance. Conductivity and emissivity describe different properties, and both appear in the calculation.

3. Radiation to Space

The surface temperature is an unknown. Solve conduction and radiation together using absolute temperature in kelvin.

Tback = (175 − 32) × 5/9 + 273.15 = 352.594444 K
q″conduction = (352.594444 − Ts) / 0.000749080
q″radiation = 0.90 × 5.670374419×10⁻⁸ × (Ts⁴ − 3⁴)
q″conduction = q″radiation
Ts ≈ 352.007509 K = 173.943517°F
q″ ≈ 783.541 W/m² = 248.381 Btu/(h·ft²)

The solved surface is cooler than the backing by about 1.06°F. A trial surface temperature is adjusted until the heat conducted through the layers equals the heat radiated away.

4. Total Heat Transfer

A = 100 ft² = 9.290304 m²
Q = q″ × A = 783.541 × 9.290304
Q ≈ 7,279 W = 7.28 kW = 24,838 Btu/h
MechanismHeat rateLocation
Conduction7.28 kWThrough the panel and coating
Convection0 kWExternal vacuum boundary
Radiation7.28 kWCoating to space
Total heat rejected7.28 kWNet through the system

The same 7.28 kW travels through the solids and leaves by radiation. Adding those two values would count that heat twice.

5. Scale to the Orbital Computing Scenario

Qfacility = 1.0 GW × 1.20 = 1.2 GW
Arequired = 1.2×10⁹ / 783.541
Arequired ≈ 1.532 million m² ≈ 16.49 million ft²
          ≈ 378 acres of emitting face

This scaling assumes the backing stays at 175°F across the entire array. Delivering heat uniformly over that area requires a separate coolant and heat-spreading design. The original article's 167°F (75°C) radiator case needs about 1.601 million m²; the warmer surface in this example gives a slightly smaller area.

6. Check the Calculator

Expect about 7.28 kW total, 173.94°F at the coating surface, and zero convection at Side B. Change the area to 200 ft². Heat rejection should double to 14.56 kW while the surface temperature and heat flux stay constant. Turn off the vacuum option and a positive convection coefficient will introduce an air-side heat-transfer path, which changes the physical problem.

Assumptions and Limits

The emitting face sees a uniform 3 K sink with view factor 1. The model excludes absorbed sunlight, Earth infrared radiation, reflected sunlight, nearby warm structures, and radiation from the panel's back face. Those environmental loads must be included when designing an actual spacecraft radiator.

The layers have constant assumed conductivities, perfect contact, equal area, and one-dimensional steady conduction. The calculation begins at a uniformly heated backing. Chip junction resistance, concentrated chip footprints, lateral spreading, heat pipes, coolant loops, deployment hardware, and transient operation require additional analysis.

Radiation equation and spacecraft thermal environment guidance are available in the NASA Passive Thermal Control Engineering Guidebook. See also the two-layer wall example and multilayer calculator.